Description
ABB 5SHY4045L0001 IGCT Power Module Technical Specifications
ABB 5SHY4045L0001 Symmetric IGCT Module for ACS6000 Medium-Voltage Drives
The ABB 5SHY4045L0001 (order code 3BHB018162R0001) is a press-pack symmetric Integrated Gate-Commutated Thyristor (IGCT) module designed for high-power industrial conversion systems. Its symmetric blocking capability allows it to block voltage in both forward and reverse directions, making it particularly suited for four-quadrant regenerative drive topologies where a separate freewheeling diode is not required. This module serves as a core switching element within ABB ACS6000 medium-voltage drive platforms, commonly deployed in steel mill reversing stands, mine hoists, and large industrial motor drives.
| Parameter | Specification |
|---|---|
| Device Type | Symmetric IGCT (S-IGCT), press-pack |
| Part Number / Order Code | 5SHY4045L0001 / 3BHB018162R0001 |
| Blocking Voltage (VDRM / VRRM) | 4500 V (bidirectional, symmetric) |
| Continuous Current | 4000 A RMS (at Tj ≤ 125°C) |
| Surge Current (ITSM) | 28,000 A (10 ms duration) |
| Turn-On / Turn-Off Time | ≤ 2.5 µs / ≤ 6 µs |
| On-State Voltage Drop | ~1.45 V (base) plus dynamic resistance |
| Frame Size | 91 mm class (approx. 220 × 140 × 80 mm) |
| Cooling Method | Forced liquid cooling (deionized water/glycol) |
| Required Coolant Flow | 12–18 L/min (maintain ΔT < 6°C) |
| Compatible Gate Driver | GVC750BE101 |
| Operating Junction Temperature | -40°C to +125°C |
| Typical Applications | ACS6000 MV drives, regenerative four-quadrant converters, steel rolling mills, mine hoists |
The symmetric design of the 5SHY4045L0001 distinguishes it from asymmetric IGCT variants: it blocks rated voltage in both directions, enabling use in current-source inverter topologies and regenerative drives without antiparallel diodes. The press-pack housing provides double-sided cooling and solder-free contacts for high thermal cycling reliability. When replacing this device, verify that the replacement matches the symmetric L0001 variant; substituting an asymmetric IGCT in the same position can lead to reverse-blocking failure during regenerative operation. The integrated GVC750BE101 gate unit executes the hard commutation required for turn-off, extracting charge carriers from the gate within microseconds.

ABB IGCT Module | ABB ACS6000 | ABB PCS6000

ABB IGCT Module | ABB ACS6000 | ABB PCS6000

ABB IGCT Module | ABB ACS6000 | ABB PCS6000