Description
- ABB CI854A (3BSE030220R1) | Dual Channel Line Redundancy Fieldbus Adapter
- ABB CI854A | Hot-Swap Profibus Master Module Compatible With 800xA DCS Platform
- ABB CI854A | Direct Replacement Communication Card For S800 I/O & Drives Connection
- ABB CI854A | Factory Tested Automation Spare Part In Stock With 12 Month Warranty
Product Core Brief
- Model: CI854A, Order Code: 3BSE030220R1
- Brand: ABB
- Series: AC 800M / System 800MxA Automation Platform
- Core Function: Acts as PROFIBUS-DP/V1 master to link AC800M controllers with field devices
- Type: PROFIBUS-DP Communication Interface Module
- Key Specs: Dual DB9 ports for line redundancy; up to 12 Mbit/s baud rate; hot-swap capable; supports cyclic & acyclic data exchange
- Condition: New Original, factory sealed, non-refurbished
⚠️ Note: CI854A is succeeded by CI854B for new projects, stock availability is limited
Product Introduction
Key Technical Specifications
| Parameter Item | Technical Data |
|---|---|
| Full Part Number | CI854A / 3BSE030220R1 |
| Supported Controller | ABB AC 800M Series |
| Communication Protocol | PROFIBUS-DP / DP-V1 Master |
| Communication Ports | Dual DB9 RS485 ports, support line redundancy |
| Maximum Baud Rate | 12 Mbit/s |
| Max Slave Nodes Per Bus | Up to 62 stations |
| Installation Base | TP854 baseplate (required accessory) |
| Hot Swap Support | Yes |
| Supply Interface | Powered via CEX bus |
| Operating Temperature | 0°C ~ +60°C |
| Storage Temperature | -40°C ~ +70°C |
| Protection Class | IP20, cabinet indoor mounting |
| Typical Application | Power plant, chemical, pulp & paper automation control |

ABB CI854A 3BSE030220R1
Installation & Configuration Guide
Stage 1: Pre-Installation Preparation (12 mins)
Shut down the target AC800M rack power supply and wait 5 minutes for capacitor discharge.
Prepare tools: ESD wrist strap, insulated screwdriver, digital camera. Export control project backup, take clear photos of PROFIBUS wiring and termination switch status.
⚠️ Important reminder: Record original module firmware revision before removal. Mismatched firmware may lead to communication handshake failure.
Stage 2: Old Module Removal (10 mins)
Check TP854 baseplate contacts for oxidation or bent pins. Remove dust gently with anti-static cloth.
Stage 3: New Module Installation (18 mins)
Align module with TP854 baseplate and push until latch locks securely. Reconnect PROFIBUS cables strictly following photo records.
Check bus termination switch: enable termination only for devices at both physical ends of the bus segment.
Stage 4: Power-On & Fieldbus Commissioning (35 mins)
Launch Control Builder software, scan hardware and verify the new communication module is recognized.
Download project configuration, execute bus scan to detect all PROFIBUS slave nodes.
Check real-time data exchange status, confirm no communication timeout alarms.
Maintain continuous operation monitoring for minimum 30 minutes before switching network back to automatic operating status.

ABB CI854A 3BSE030220R1
Frequently Asked Questions (FAQ)
Yes. CI854A cannot work independently. The TP854 baseplate provides CEX bus connection and two DB9 PROFIBUS sockets.
Hardware supports hot-swap. Still set the fieldbus network to maintenance status in advance. Unexpected bus interruption may trigger interlock protection for field devices.
Not plug-and-play. CI854B is upgraded successor. Hardware and project configuration adjustments are required. Avoid direct swap without software verification.
Verify PROFIBUS A/B cable assignment and termination switch settings. Reversed A/B signal wires or incorrect termination are the most frequent root causes.
Yes. Two CI854A modules can be configured as redundant PROFIBUS master pair together with redundant AC800M CPU to enhance system availability.
Classified as critical EOL communication spare. Arrange last-time-buy for running legacy AC800M sites. Maintain 1 unit buffer stock; vendor consignment stock helps reduce occupied capital.