ABB PCS6000 GBU72 Grid Breaker Unit — 3BHE055094R0002, Grid-Side Breaker Assembly
| Attribute | Rating |
|---|---|
| Unit type | Grid Breaker Unit (GBU) — grid-side circuit breaker assembly of the PCS6000 full-size power converter |
| ABB material / order code | 3BHE055094R0002, type GBU72 |
| System / application | ABB PCS6000 medium-voltage full-size power converter for wind and tidal turbines, 1CL and 2CL configurations |
| Function | Making, breaking and short-circuit breaking on the grid side, plus disconnecting and earthing of the grid-side cables |
| Integrated devices | Circuit breaker (GBM — Grid Breaker Module) plus a three-position switch for closed / test / earthed positions |
| Operating mechanism | Manual only — three-position switch driven by hand cranks, breaker charged with a charging lever; no remote electrical operation of the disconnector |
| Mounting arrangement | Breaker and three-position switch on a common mounting plate; the GBM is inserted into the GBU frame |
| Rated voltage | Converter grid-side MV level, typically 3.3 kV in PCS6000 wind applications — verify against the project nameplate |
| Short-time current | Grid connection rated approx. 3 kA rms, 3 s, rating factor 0.85 to cover converter operation |
| Breaking duty | Must clear converter fault current within the ABB limit of max. 75 ms protection trip time, 500 ms maximum safety trip time |
| Earthing logic | Three-position switch prepares earth connection at zero current; earthing is established by closing the breaker with the switch in earth position |
| Cabinet environment | Standard cabinet IP54, sound pressure level below 75 dB(A) |