GE 8851-LC-MT | SafetyNet Controller | SIL 2 / OEM

$2,350.00

GE 8851-LC-MT occupies the controller position in the PAC8000 SafetyNet architecture.
Brand model:GE 
Product Name:8851-LC-MT
Warranty: 1 year
Origin:USA
HS code:85389000.00
Inventory: Spot/Futures
Goods condition: Brand new
Delivery time: 3-4days/1month

Categories: , Model/SKU: GE 8851-LC-MT

Get a Quote / Inquiry

Phone/WhatsApp/Wechat:
WeChat QR Code WhatsApp

Description

  • Model & Brand: GE / MTL 8851-LC-MT

  • Series: PAC8000 SafetyNet
  • Part Type: SafetyNet Logic Controller / Safety Controller
  • Physical Dimensions: Approximately 69 × 232 × 138 mm (W × L × H)
  • Estimated Shipping Weight: Approximately 1.35 kg
  • What’s in the Box: 8851-LC-MT SafetyNet controller, ESD protection, protective packaging, and applicable QC/inspection documentation. The 8913-PS-AC power supply, carrier, I/O modules, and programming accessories are separate components unless explicitly included.

Product Introduction

The GE 8851-LC-MT occupies the controller position in the PAC8000 SafetyNet architecture. It stores and executes the SafetyNet application program, communicates with local I/O through the internal Railbus, exchanges information over the Ethernet network, and provides serial communication with external devices. It also manages the master/standby redundancy strategy when the appropriate redundant configuration is installed.

For safety-related maintenance, this is a controller rather than an ordinary PLC I/O module. The unit is documented for SIL 2 operation using a 1oo1D architecture, with optional redundancy and extensive internal diagnostics. That certification boundary belongs to the specified SafetyNet system configuration; it should not be transferred automatically to an arbitrary replacement board or mixed-generation installation.

Core Technical Specifications

Parameter Value
Manufacturer / Family GE / MTL PAC8000 SafetyNet
Model 8851-LC-MT
Product Type SafetyNet Logic Controller
Primary Function Safety application execution and SafetyNet communications
Safety Architecture 1oo1D
Safety Capability SIL 2
Controller Power 12 VDC from 8913-PS-AC
Controller Current 0.4 A typical / 0.5 A maximum
System Power Supply 15 mA maximum
Local I/O Interface Internal Railbus
Maximum Local I/O Up to 64 I/O modules in the SafetyNet node architecture
Ethernet High-speed Ethernet LAN
Ethernet Role SafetyNet/node, workstation, HMI, historian and engineering communications
Serial Interfaces 2 × RS-485
Serial Application Remote serial-device communication
Programming Environment PAC8000 Workbench
Application Storage SafetyNet application stored and executed by controller
Event Logging Up to 8,000 events
Redundancy Optional master/standby arrangement
Hot Maintenance System-dependent; follow the approved SafetyNet maintenance procedure
Hazardous Location Class I, Division 2, Groups A–D, T4 for applicable certified configuration
Zone Classification Zone 2 / EEx nL IIC T4 for applicable certified configuration
Dimensions 69 × 232 × 138 mm
Approx. Weight 1.35 kg
Controller Power Source 8913-PS-AC
Firmware SafetyNet controller firmware / application dependent
Operating Temperature Verify exact certification/environmental configuration
Storage Temperature Verify exact equipment documentation
Lifecycle Position Legacy / Controlled Spare

The controller’s documented power requirement is 12 VDC, 0.4 A typical and 0.5 A maximum, supplied from the 8913-PS-AC power system. At the maximum controller current, that represents about 6 W of controller-side electrical consumption, while the total SafetyNet system must be budgeted separately.

The 2 RS-485 ports, Ethernet connectivity, Railbus interface, application execution, and redundancy management make the 8851-LC-MT the central processing element of a SafetyNet node. It is not a field I/O slice, and substituting a generic PAC8000 controller does not preserve the same safety function.

GE 8851-LC-MT

GE 8851-LC-MT

🚨 Global Compliance & Industry Certifications

  • IEC 61508 / SIL 2: The 8851-LC-MT is documented for SIL 2 safety applications in 1oo1D architecture. This is the most important safety characteristic for procurement and configuration control.
  • Class I, Division 2: The documented hazardous-location configuration is Class I, Division 2, Groups A, B, C, D, T4. This classification controls where the equipment can be installed around potentially flammable gas or vapor.
  • Zone 2: The SafetyNet controller is also identified with Zone 2 / EEx nL IIC T4 certification for applicable configurations.
  • CE Mark: Verify the applicable PAC8000/SafetyNet declaration for the exact hardware and certificate revision.
  • UL/cUL: Verify the specific SafetyNet system certification and installation conditions.
  • ATEX / IECEx: The hazardous-area designation must be checked against the exact controller revision, carrier, power supply, and field installation.
  • Marine / DNV GL: No independent DNV GL approval should be assumed without project-specific documentation.
  • Country of Origin: Establish from manufacturing traceability for the actual controller.
  • HS Classification: Confirm the final tariff code with the destination-country customs broker.

The hazardous-location ratings are configuration-sensitive. A Class I Division 2 or Zone 2 designation does not mean an individually removed controller can be installed in any classified area without the associated certified power, carrier, wiring, and environmental conditions.

Verify specific lot certifications with OEM.

🚨 Long-Term Storage & Asset Preservation Guide

Keep the 8851-LC-MT in an ESD shielding bag until installation. Protect the Ethernet and RS-485 connectors, Railbus interface, and mounting surfaces from dust and mechanical impact.

The controller uses application memory and electronic storage rather than the large electrolytic-capacitor power stage found in legacy drive power boards. Even so, maintain a dry warehouse with no condensation; a practical long-term target below approximately 60% RH reduces corrosion risk around connectors and PCB surfaces.

Record the controller’s firmware revision, application-project revision, serial number, and redundancy role before placing it into strategic stock. A SafetyNet CPU without the correct application backup can require substantially more recovery work than a documented spare.

Do not apply an arbitrary external 12 V supply to a stored controller. The specified 12 VDC source is provided through the SafetyNet power architecture, and bench testing should reproduce the approved system conditions.

Physical Installation Prerequisites

Install the 8851-LC-MT in the SafetyNet node using the specified controller/carrier arrangement and 8913-PS-AC power system. The controller dimensions are approximately 69 × 232 × 138 mm, so allow sufficient room for the rear connections and cable bend radius.

The controller’s power input is 12 VDC, supplied through the specified SafetyNet power arrangement. Do not substitute a generic 24 VDC PLC supply directly into the controller.

Maintain the original Ethernet and RS-485 network assignments. The two RS-485 ports may connect to external serial devices, while Ethernet supports the SafetyNet/node communications architecture. Port identity should therefore be recorded before replacement.

Preserve the cabinet’s designed ventilation and service access. There is no defensible basis for imposing a universal 50 mm rule on this controller; use the actual cabinet arrangement and certified installation drawing.

For hazardous-area installations, retain the certified segregation, wiring, grounding, power-supply, and enclosure conditions. Do not remove or install the controller under power unless the approved SafetyNet maintenance procedure specifically permits that operation.

Buyer’s FAQ — Logistics & Compliance Focus

Q: What HS Tariff Code should be used for 8851-LC-MT?
A: It is a dedicated industrial safety controller, but the final Harmonized System classification depends on the importing country’s tariff schedule and customs interpretation. Have the importer or broker confirm the final code before the commercial invoice is issued.

Q: Can I use “USA” as COO because some catalogs list the controller as US-origin?
A: Only when manufacturing documentation supports it. One current industrial record lists the Country of Origin as USA, but that should not replace unit- or lot-level traceability for a specific shipment.

Q: Does the 8851-LC-MT arrive with the latest firmware pre-loaded?
A: Do not assume it. The controller stores and executes the SafetyNet application downloaded from , while the installed application and firmware revision can be tied to the site’s approved safety configuration. Verify the controller software baseline before commissioning.

Q: What should shipping insurance and physical packing cover?
A: Insure the controller for its documented commercial replacement value and photograph the nameplate, connectors, enclosure, and packaging before dispatch. Use ESD protection, rigid connector protection, moisture control, and internal cushioning; the approximately 1.35 kg controller should remain immobilized throughout transportation.

mingpian