Description
-
Brand: FOXBORO / Invensys
-
Full Model Number: 2AX-ALM-AR
-
System/Series Family: FOXBORO SPEC 200 process control hardware
-
Core Function: Dual absolute alarm module with relay outputs for monitoring two analog input conditions
-
Top 3 Technical Specs: 0–10 VDC input; two independently adjustable alarm setpoints; relay contacts rated up to 28 VDC and 100 mA resistive load
-
Stock Status: Confirm actual inventory, condition, and test records before ordering
The manufacturer’s documentation identifies the 2AX+ALM-AR designation with a dual absolute alarm, relay-output configuration. It specifies 0–10 VDC inputs and a maximum relay contact rating of 28 VDC at 100 mA for resistive loads.
Quality Assurance SOP
The following checks define a suitable pre-shipment inspection process for this legacy alarm module. Actual test results must be recorded for the individual unit; the procedure below is not a claim that a specific unit has already passed testing.
-
OEM identification inspection: Examine the manufacturer markings, full part number, revision identifiers, connector layout, and visible board construction.
-
Physical condition assessment: Inspect the circuit board, components, contacts, connectors, and mounting surfaces for corrosion, cracking, contamination, or repair damage.
-
Configuration verification: Confirm the
2AX-ALM-ARdesignation and verify whether the order requires the card alone or a complete assembly. -
Power-up verification: Using a suitable SPEC 200 test setup, apply the documented ±15 VDC supplies within specified tolerances. Check for abnormal current draw, overheating, or visible damage.
-
Alarm threshold testing: Apply controlled 0–10 VDC test signals and verify both alarm setpoints, switching behavior, and reset behavior against the applicable specifications.
-
Relay output verification: Check contact continuity in normal and alarm states. Confirm that the outputs operate within the documented voltage and current limits.
-
Response and stability checks: Where the test equipment permits, measure response time and verify repeatability at representative input values.
-
Final documentation: Record the test setup, measured results, inspection findings, unit identification, and packaging condition.
Test limitation: A standard communication handshake is not applicable to this analog alarm card in the same way it is to a networked controller. Functional verification should focus on input response, alarm thresholds, and relay switching.

FOXBORO 2AX-ALM-AR
CRO-Driven Buyer FAQ
Is the FOXBORO 2AX-ALM-AR discontinued?
Available supplier listings identify the model as discontinued by the manufacturer. Treat it as a legacy spare and verify current stock, condition, and traceability before placing an order.
Can I replace the 2AX-ALM-AR without shutting down the system?
Do not assume that live replacement is permitted. Confirm the SPEC 200 nest assembly’s service requirements and the site’s isolation procedure. Because the module uses relay outputs in process alarm circuits, establish a safe method for managing alarm coverage during maintenance.
What are the main electrical specifications?
The manufacturer’s documentation specifies 0–10 VDC inputs, nominal +15 VDC and −15 VDC supplies, and relay contacts rated up to 28 VDC at 100 mA resistive load. The documented response time is approximately 15 ±5 milliseconds under the stated test conditions. Check the original technical documentation before applying these limits to a specific installation.
What warranty and technical support are available?
Warranty duration and coverage depend on the supplied unit’s condition and the terms confirmed in the quotation. Request written confirmation of the warranty period, functional test coverage, return conditions, and available technical support. Do not assume that an original manufacturer’s warranty remains valid for discontinued inventory.
What information should I provide for a replacement quotation?
Provide the existing card’s nameplate photograph, the complete part number, the nest assembly identification, the required quantity, and the desired condition. If possible, include the existing alarm setpoints and relay wiring details. This information helps verify the correct hardware configuration before shipment.